Bajardi: bobonazarov exson


Tok transformatorlarining yuki



Yüklə 0,53 Mb.
səhifə8/8
tarix17.08.2023
ölçüsü0,53 Mb.
#139682
1   2   3   4   5   6   7   8
Bajardi bobonazarov exson (1)

Tok transformatorlarining yuki
Tok transformatorlari xatoligi uning yuki miqdoriga teng.
Tok transformatorining ikkilamchi chulg‘amidagi qarshilik quyidagicha topiladi:
Zyu=U2/I2,
bu yerda: U2 va I2 – ikklamchi chulg‘amning kuchlanishi va toki (4.2- a rasm).

Zyu ni topish uchun U2 kuchlanishni hisobga olish kerakU2 kuchlanish esa yuk qarshiligi Zyu dan tok oqqandagi kuchlanishni tushuviga teng (4.2-rasm).
Yukning qarshiligi simning qarshiligi ZS va relening qarshiligi ZR lardan iborat: ZYu=ZS+ZR, unda, U2=I2∙ZYu ning kattaligi tok transformatorlarini ulanish sxemalariga bog‘liq. ZYu ni kattaligi esa qisqa tutashuv turiga bog‘liq.
Tok transformatori TA ning ikkilamchi chulg‘amini uzish mumkin emas, chunki I2=0 bo‘lsa, hamma birlamchi tok magnitlovchi tokka aylanib qoladi. Bu esa oqim Ôt ni oshishiga sabab bo‘ladi, natijada katta oqimga proporsional E2 hosil bo‘ladi, uning qiymati 1,5 kV gacha yetadi, natijada izolyatsiya teshilishi mumkin, bu esa qisqa tutashuvga olib keladi. Katta oqim ta’sirida po‘lat o‘zak qizib, kengayib ketadi.
Ikkilamchi chulg‘amdagi yukning miqdori tok transformatorining xatoligiga ta’sir etadi. ZYu kam bo‘lgani sari o‘lchov aniqlashadi. Xulosa qilib aytganda, TA ning normal ish holati qisqa tutashuv rejimiga yaqin.


Tok transformatorlarining yukini kamaytirish uchun ikkita tok trans- formatorini ketma-ket ulash mumkin, ya’ni ular bir fazada o‘rnatiladi va bir xil nt transformatsiya koeffitsiyentiga ega bo‘ladi.