Here is PLC program to Control Level of Series Tanks, along with program explanation and run time test
cases.
List of Inputs and Outputs
I:1/14 & I:1/15 = Start & Stop
(Input)
I:1/0
= LHST1 high level switch of storage tank
(Input)
I:1/1
= LLST1 low level switch of storage tank (Input)
I:1/2
= LHST2 high level switch of feeder tank (Input)
I:1/3
= LLST2 low level switch of feeder tank (Input)
O:2/0
= Inlet valve
(Output)
Ladder
diagram
to
control
series
tanks
Program Description
RUNG000 is used for latching the bit B3:0/0 through which Master Start and Stop can be performed.
Memory Bit is used here to save an output terminal.
RUNG001 performs controlling of Inlet Valve which is connected to O:2/0 of output module.
O:2/0 energizes when I:1/1 or I:1/3 goes high which is set by Low level switch of storage tank or by low level
switch of feeder tank respectively.
Similarly it is closed when high level of storage and feeder tank detected.