Velocis Solutions Caspian Plaza II, 12th Floor, Baku az1065



Yüklə 1,66 Mb.
Pdf görüntüsü
səhifə17/25
tarix02.01.2022
ölçüsü1,66 Mb.
#41417
1   ...   13   14   15   16   17   18   19   20   ...   25
Chapter 7-Pumps

CHAPTER 6 

 

VELOCIS SOLUTIONS @2018 

 

                         14 



 

At low values of volume flow rate, the combined net head is equal to the sum of the net head of 

each  pump  by  itself.  However,  to  avoid  pump  damage  and  loss  of  combined  net  head,  any 

individual  pump  should  be  shut  off  and  bypassed  at  flow  rates  larger  than  that  pump’s  free 

delivery, as indicated by the vertical dashed red lines. If the three pumps were identical, it would 

not be necessary to turn off any of the pumps, since the free delivery of each pump would occur 

at the same volume flow rate. 

 

When two or more identical (or similar) pumps are operated in parallel, their individual volume 



flow rates (rather than net heads) are summed. In practice, several pumps may be combined in 

parallel to deliver a large volume flow rate. Ideally all the pumps should be identical so that we 

don’t need to worry about shutting any of them off. Also, it is wise to install check valves in each 

branch so that when a pump needs to be shut down

 

(for maintenance or when the required flow 



rate is low), backflow through the pump is avoided. Note that the extra valves and piping required 

for a parallel pump network add additional head losses to the system; thus the overall performance 

of the combined pumps suffers somewhat. 

 

                         



 

 

                                     Figure 7.11: Performance curve for pumps in parallel 



 

At a low value of net head, the combined capacity is equal to the sum of the capacity of each pump 

by  itself.  However, to  avoid pump  damage  and  loss  of  combined  capacity, any individual pump 

should be shut off at net heads larger than that pump’s shutoff head, as indicated by the horizontal 

dashed gray lines. That pump’s branch should also be blocked with a valve to avoid reverse flow. 

If the three pumps were identical, it would not be necessary to turn off any of the pumps, since 

the shutoff head of each pump would occur at the same net head. 


Yüklə 1,66 Mb.

Dostları ilə paylaş:
1   ...   13   14   15   16   17   18   19   20   ...   25




Verilənlər bazası müəlliflik hüququ ilə müdafiə olunur ©azkurs.org 2024
rəhbərliyinə müraciət

gir | qeydiyyatdan keç
    Ana səhifə


yükləyin