RUNG003 & RUNG004 operates Agitator Motor M1 with address O:2/2. When the tank is full with Material A
and B, Level High (Level Material B) of tank 1 is detected. This detection energizes O:2/2 and enables ON timer
with address T4:0. Agitator Motor M1 is connected to the address O:2/2. So when O:2/2 energizes, Motor
Agitator M1 starts the mixing process and mixes Material A and B for 20secs which is a preset of Timer ON.
When Pre = Acc, T4;0/DN bit goes high turning off the agitator motor M1.
RUNG005 is for Outlet Valve 1 with address O:2/3. It is operated when
the entire mixing process is
completed that is when Pre= Acc = 20secs. And this is closed when LLS is again detected.
Similarly Mixing Process Tank 2 is operated.