I:1/0
=
Level High Switch
(Input)
I:1/1
=
Level Low Switch
(Input)
O:2/0
=
Inlet Valve
(Output)
O:2/1
=
Outlet Valve
(Output)
I:1/14 = Start
(Input)
I:1/15 = Stop
(Input)
Ladder
Diagram
to
control
this
process
Program Description
RUNG000 is simply for latching a coil and master start-stop buttons.
RUNG001 is to control the outlet valve through O:2/1. This is done when Level High is detected.
Latching of Output O:2/1 is done because when High Level is detected, input to RUNG001 is temporary, like
Push Button. So in order to keep outlet valve open until the Level Low I:1/1 is detected, latching is done. XIO of
Level Low Switch is connected in series so that when Level Low is detected, it goes true closing the outlet valve.
Similarly in RUNG002, it works exactly same. The only difference in RUNG002 is that extra I:1/14 contact in
parallel with LLS.
Suppose when the system is started and the tank is partially filled, neither LHS nor LLS is detected, in this
case, outlet and inlet valves remain closed while inlet valve should open to start filling the tank because it’s