Ladder Logic (lad) for S7-300 and S7-400 Programming


  ---( # )---  Midline Output



Yüklə 1,39 Mb.
Pdf görüntüsü
səhifə3/16
tarix05.05.2020
ölçüsü1,39 Mb.
#31077
1   2   3   4   5   6   7   8   9   ...   16
STEP 7 - Ladder Logic for S7-300 and S7-400


1.7 
---( # )---  Midline Output 
Symbol 
 
 ---( # )--- 
 
Parameter 
Data Type 
Memory Area 
Description 
 
BOOL 
I, Q, M, *L, D 
Assigned bit 
* An L area address can only be used if it is declared TEMP in the variable declaration table of a 
logic block (FC, FB, OB). 
Description  
---( # )--- (Midline Output) is an intermediate assigning element which saves the RLO bit (power 
flow status) to a specified 
. The midline output element saves the logical result of the 
preceding branch elements. In series with other contacts, ---( # )--- is inserted like a contact. A ---( 
# )--- element may never be connected to the power rail or directly after a branch connection or at 
the end of a branch. A negated ---( # )--- can be created by using the ---|NOT|--- (invert power flow) 
element. 

 
Bit Logic Instructions
 
 
1.8 ---( R )  Reset Coil
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
Reference Manual, 04/2017, A5E41524738-AA 
19 
MCR (Master Control Relay) dependency 
MCR dependency is activated only if a midline output coil is placed inside an active MCR zone. 
Within an activated MCR zone, if the MCR is on and there is power flow to a midline output coil; the 
addressed bit is set to the current status of power flow. If the MCR is off, a logic "0" is written to the 
specified address regardless of power flow status. 
Status word 
 
 
BR 
CC 1 
CC 0 
OV 
OS 
OR 
STA 
RLO 
/FC 
writes: 









Example 
M 1.1
M 2.2
Q 4.0
I 1.0 I 1.1
M 1.1 has the RLO
M 0.0 has the RLO
M 2.2 has the RLO of the entire bit logic combination
I 1.0 I 1.1
I 2.2 I 1.3
M 0.0
I 1.0 I 1.1
I 2.2 I 1.3
 NOT
(   )
(#)
(#)
 NOT
(#)
NOT
 
1.8 
---( R )  Reset Coil 
Symbol 
 
---( R ) 
 
Parameter 
Data Type 
Memory Area 
Description 
 
BOOL 
I, Q, M, L, D, T, C 
Reset bit 
Description  
---( R ) (Reset Coil) is executed only if the RLO of the preceding instructions is "1" (power flows to 
the coil). If power flows to the coil (RLO is "1"), the specified 
 of the element is reset to 
"0". A RLO of "0" (no power flow to the coil) has no effect and the state of the element's specified 
address remains unchanged. The 
 may also be a timer (T no.) whose timer value is 
reset to "0" or a counter (C no.) whose counter value is reset to "0". 

Bit Logic Instructions
 
1.8 ---( R )  Reset Coil
 
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
20 
Reference Manual, 04/2017, A5E41524738-AA 
MCR (Master Control Relay) dependency 
MCR dependency is activated only if a reset coil is placed inside an active MCR zone. Within an 
activated MCR zone, if the MCR is on and there is power flow to a reset coil; the addressed bit is 
reset to the "0" state. If the MCR is off, the current state of the element's specified address remains 
unchanged regardless of power flow status. 
Status word 
 
 
BR 
CC 1 
CC 0 
OV 
OS 
OR 
STA 
RLO 
/FC 
writes: 









Example 
I 0.0
I 0.1
I 0.2
R
Q 4.0
T1
I 0.3
C1
I 0.4
R
R
Network 3
Network 2
Network 1
 
 
The signal state of output Q4.0 is reset to "0" if one of the following conditions exists: 
The signal state is "1" at inputs I0.0 and I0.1 
Or the signal state is "0" at input I0.2. 
If the RLO is "0", the signal state of output Q4.0 remains unchanged. 
The signal state of timer T1 is only reset if: 
the signal state is "1" at input I0.3. 
The signal state of counter C1 is only reset if: 
the signal state is "1" at input I0.4. 
 
If the example rungs are within an activated MCR zone: 
When MCR is on, Q4.0, T1, and C1 are reset as described above. 
When MCR is off, Q4.0, T1, and C1 are left unchanged regardless of RLO state (power flow 
status). 

 
Bit Logic Instructions
 
 
1.9 ---( S )  Set Coil
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
Reference Manual, 04/2017, A5E41524738-AA 
21 
1.9 
---( S )  Set Coil 
Symbol 
 
---( S ) 
 
Parameter 
Data Type 
Memory Area 
Description 
 
BOOL 
I, Q, M, L, D 
Set bit 
Description  
---( S ) (Set Coil) is executed only if the RLO of the preceding instructions is "1" (power flows to the 
coil). If the RLO is "1" the specified 
 of the element is set to "1". 
An RLO = 0 has no effect and the current state of the element's specified address remains 
unchanged. 
MCR (Master Control Relay) dependency 
MCR dependency is activated only if a set coil is placed inside an active MCR zone. Within an 
activated MCR zone, if the MCR is on and there is power flow to a set coil; the addressed bit is set 
to the "1" state. If the MCR is off, the current state of the element's specified address remains 
unchanged regardless of power flow status. 
Status word 
 
 
BR 
CC 1 
CC 0 
OV 
OS 
OR 
STA 
RLO 
/FC 
writes: 









Example 
I 0.0
I 0.1
I 0.2
S
Q 4.0
 
 
The signal state of output Q4.0 is "1" if one of the following conditions exists: 
The signal state is "1" at inputs I0.0 and I0.1 
Or the signal state is "0" at input I0.2. 
If the RLO is "0", the signal state of output Q4.0 remains unchanged. 
 

Bit Logic Instructions
 
1.10 RS  Reset-Set Flip Flop
 
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
22 
Reference Manual, 04/2017, A5E41524738-AA 
If the example rungs are within an activated MCR zone: 
When MCR is on, Q4.0 is set as described above. 
When MCR is off, Q4.0 is left unchanged regardless of RLO state (power flow status). 
1.10 
RS  Reset-Set Flip Flop 
Symbol 
RS
S
Q

R
 
 
Parameter 
Data Type 
Memory Area 
Description 
 
BOOL 
I, Q, M, L, D 
Set or reset bit 

BOOL 
I, Q, M, L, D 
Enabled reset instruction 

BOOL 
I, Q, M, L, D 
Enabled reset instruction 

BOOL 
I, Q, M, L, D 
Signal state of 
 
Description 
RS (Reset-Set Flip Flop) is reset if the signal state is "1" at the R input, and "0" at the S input. 
Otherwise, if the signal state is "0" at the R input and "1" at the S input, the flip flop is set. If the 
RLO is "1" at both inputs, the order is of primary importance. The RS flip flop executes first the 
reset instruction then the set instruction at the specified 
, so that this address remains 
set for the remainder of program scanning. 
The S (Set) and R (Reset) instructions are executed only when the RLO is "1". RLO "0" has no 
effect on these instructions and the address specified in the instruction remains unchanged. 
MCR (Master Control Relay) dependency 
MCR dependency is activated only if a RS flip flop is placed inside an active MCR zone. Within an 
activated MCR zone, if the MCR is on, the addressed bit is reset to "0" or set to "1" as described 
above. If the MCR is off, the current state of the specified address remains unchanged regardless 
of input states. 
Status word 
 
 
BR 
CC 1 
CC 0 
OV 
OS 
OR 
STA 
RLO 
/FC 
writes: 










 
Bit Logic Instructions
 
 
1.11 SR  Set-Reset Flip Flop
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
Reference Manual, 04/2017, A5E41524738-AA 
23 
Example 
RS
R
Q
M 0.0
S
I 0.0
I 0.1
Q 4.0
 
 
If the signal state is "1" at input I0.0 and "0" at I0.1, memory bit M0.0 is set and output Q4.0 is "0". 
Otherwise, if the signal state at input I0.0 is "0" and at I0.1 is "1", memory bit M0.0 is reset and 
output Q4.0 is "1". If both signal states are "0", nothing is changed. If both signal states are "1", the 
set instruction dominates because of the order; M0.0 is set and Q4.0 is "1". 
 
If the example is within an activated MCR zone: 
When MCR is on, Q4.0 is reset or set as described above. 
When MCR is off, Q4.0 is left unchanged regardless of input states. 
1.11 
SR  Set-Reset Flip Flop 
Symbol 
SR
S
Q

R
 
 
Parameter 
Data Type 
Memory Area 
Description 
 
BOOL 
I, Q, M, L, D 
Set or reset bit 

BOOL 
I, Q, M, L, D 
Enable set instruction 

BOOL 
I, Q, M, L, D 
Enable reset instruction 

BOOL 
I, Q, M, L, D 
Signal state of 
 
Description 
SR (Set-Reset Flip Flop) is set if the signal state is "1" at the S input, and "0" at the R input. 
Otherwise, if the signal state is "0" at the S input and "1" at the R input, the flip flop is reset. If the 
RLO is "1" at both inputs, the order is of primary importance. The SR flip flop executes first the set 
instruction then the reset instruction at the specified 
, so that this address remains reset 
for the remainder of program scanning. 
The S (Set) and R (Reset) instructions are executed only when the RLO is "1". RLO "0" has no 
effect on these instructions and the address specified in the instruction remains unchanged. 
MCR (Master Control Relay) dependency 
MCR dependency is activated only if a SR flip flop is placed inside an active MCR zone. Within an 
activated MCR zone, if the MCR is on ; the addressed bit is set to "1" or reset to "0" as described 

Bit Logic Instructions
 
1.12 ---( N )---  Negative RLO Edge Detection
 
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
24 
Reference Manual, 04/2017, A5E41524738-AA 
above. If the MCR is off, the current state of the specified address remains unchanged regardless 
of input states. 
Status word 
 
 
BR 
CC1 
CC0 
OV 
OS 
OR 
STA 
RLO 
/FC 
writes: 









Example 
SR
S
Q
M 0.0
R
I 0.0
I 0.1
Q 4.0
 
 
If the signal state is "1" at input I0.0 and "0" at I0.1, memory bit M0.0 is set and output Q4.0 is "1". 
Otherwise, if the signal state at input I0.0 is "0" and at I0.1 is "1", memory bit M0.0 is reset and 
output Q4.0 is "0". If both signal states are "0", nothing is changed. If both signal states are "1", the 
reset instruction dominates because of the order; M0.0 is reset and Q4.0 is "0". 
 
If the example is within an activated MCR zone: 
When MCR is on, Q4.0 is set or reset as described above. 
When MCR is off, Q4.0 is left unchanged regardless of input states. 
1.12 
---( N )---  Negative RLO Edge Detection 
Symbol 
 
---( N ) 
 
Parameter 
Data Type 
Memory Area 
Description 
 
BOOL 
I, Q, M, L, D 
Edge memory bit, storing the previous 
signal state of RLO 
Description 
---( N )--- (Negative RLO Edge Detection) detects a signal change in the address from "1" to "0" 
and displays it as RLO = "1" after the instruction. The current signal state in the RLO is compared 
with the signal state of the address, the edge memory bit. If the signal state of the address is "1" 
and the RLO was "0" before the instruction, the RLO will be "1" (pulse) after this instruction, and "0" 
in all other cases. The RLO prior to the instruction is stored in the address. 

 
Bit Logic Instructions
 
 
1.13 ---( P )---  Positive RLO Edge Detection
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
Reference Manual, 04/2017, A5E41524738-AA 
25 
Status word 
 
 
BR 
CC 1 
CC 0 
OV 
OS 
OR 
STA 
RLO 
/FC 
writes: 









Example 
N
M 0.0
I 0.0
I 0.1
I 0.2
JMP
CAS1
 
 
The edge memory bit M0.0 saves the old RLO state. When there is a signal change at the RLO 
from "1" to "0", the program jumps to label CAS1. 
1.13 
---( P )---  Positive RLO Edge Detection 
Symbol 
 
 ---( P )--- 
 
Parameter 
Data Type 
Memory Area 
Description 
 
BOOL 
I, Q, M, L, D 
Edge memory bit, storing the previous 
signal state of RLO 
Description  
---( P )--- (Positive RLO Edge Detection) detects a signal change in the address from "0" to "1" and 
displays it as RLO = "1" after the instruction. The current signal state in the RLO is compared with 
the signal state of the address, the edge memory bit. If the signal state of the address is "0" and the 
RLO was "1" before the instruction, the RLO will be "1" (pulse) after this instruction, and "0" in all 
other cases. The RLO prior to the instruction is stored in the address. 
Status word 
 
 
BR 
CC1 
CC0 
OV 
OS 
OR 
STA 
RLO 
/FC 
writes: 










Bit Logic Instructions
 
1.14 ---(SAVE)  Save RLO into BR Memory
 
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
26 
Reference Manual, 04/2017, A5E41524738-AA 
Example 
CAS1
P
M 0.0
JMP
I 0.0
I 0.1
I 0.2
 
 
The edge memory bit M0.0 saves the old RLO state. When there is a signal change at the RLO 
from "0" to "1", the program jumps to label CAS1. 
1.14 
---(SAVE)  Save RLO into BR Memory 
Symbol 
---( SAVE ) 
Description  
---(SAVE) (Save RLO into BR Memory) saves the RLO to the BR bit of the status word. The first 
check bit /FC is not reset. For this reason, the status of the BR bit is included in the AND logic 
operation in the next network. 
For the instruction "SAVE" (LAD, FBD, STL), the following applies and not the recommended use 
specified in the manual and online help: 
We do not recommend that you use SAVE and then check the BR bit in the same block or in 
subordinate blocks, because the BR bit can be modified by many instructions occurring inbetween. 
It is advisable to use the SAVE instruction before exiting a block, since the ENO output (= BR bit) is 
then set to the value of the RLO bit and you can then check for errors in the block. 
Status word 
 
 
BR 
CC 1 
CC 0 
OV 
OS 
OR 
STA 
RLO 
/FC 
writes: 









Example 
SAVE
I 0.0
I 0.1
I 0.2
 
 

 
Bit Logic Instructions
 
 
1.15 NEG  Address Negative Edge Detection
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
Reference Manual, 04/2017, A5E41524738-AA 
27 
The status of the rung (=RLO) is saved to the BR bit. 
1.15 
NEG  Address Negative Edge Detection 
Symbol 
NEG
M_BIT
Q


 
 
Parameter 
Data Type 
Memory Area 
Description 
 
BOOL 
I, Q, M, L, D 
Scanned signal 
 
BOOL 
I, Q, M, L, D 
M_BIT edge memory bit, storing the 
previous signal state of  

BOOL 
I, Q, M, L, D 
One shot output 
Description 
NEG (Address Negative Edge Detection) compares the signal state of  with the signal 
state from the previous scan, which is stored in 
. If the current RLO state is "0" and the 
previous state was "1" (detection of negative edge), the RLO bit will be "1" after this instruction. 
Status word 
 
BR 
CC 1 
CC 0 
OV 
OS 
OR 
STA 
RLO 
/FC 
writes: 









Example 
NEG
M_BIT
Q
I 0.3
M 0.0
I 0.0
(  )
I 0.1 I 0.2
I 0.4 Q 4.0
 
 
 
The signal state at output Q4.0 is "1" if the following conditions exist: 

  The signal state is "1" at inputs I0.0 and I0.1 and I0.2 

  And there is a negative edge at input I0.3 

  And the signal state is "1" at input I0.4 

Bit Logic Instructions
 
1.16 POS  Address Positive Edge Detection
 
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
28 
Reference Manual, 04/2017, A5E41524738-AA 
1.16 
POS  Address Positive Edge Detection 
Symbol  
POS
M_BIT
Q


 
 
Parameter 
Data Type 
Memory Area 
Description 
 
BOOL 
I, Q, M, L, D 
Scanned signal 
 
BOOL 
I, Q, M, L, D 
M_BIT edge memory bit, storing the 
previous signal state of  

BOOL 
I, Q, M, L, D 
One shot output 
Description 
POS (Address Positive Edge Detection) compares the signal state of  with the signal 
state from the previous scan, which is stored in 
. If the current RLO state is "1" and the 
previous state was "0" (detection of rising edge), the RLO bit will be "1" after this instruction. 
Status word 
 
 
BR 
CC 1 
CC 0 
OV 
OS 
OR 
STA 
RLO 
/FC 
writes: 









Example 
POS
M_BIT
Q
I 0.3
M 0.0
I 0.0
(  )
I 0.1 I 0.2
I 0.4 Q 4.0
 
 
 
The signal state at output Q4.0 is "1" if the following conditions exist: 

  The signal state is "1" at inputs I0.0 and I0.1 and I0.2 

  And there is a positive edge at input I0.3 

  And the signal state is "1" at input I0.4 

 
Bit Logic Instructions
 
 
1.17 Immediate Read
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
Reference Manual, 04/2017, A5E41524738-AA 
29 
1.17 
Immediate Read 
Description  
For the Immediate Read function, a network of symbols must be created as shown in the example 
below. 
For time-critical applications, the current state of a digital input may be read faster than the normal 
case of once per OB1 scan cycle. An Immediate Read gets the state of a digital input from an input 
module at the time the Immediate Read rung is scanned. Otherwise, you must wait for the end of 
the next OB1 scan cycle when the I memory area is updated with the P memory state. 
To perform an immediate read of an input (or inputs) from an input module, use the peripheral input 
(PI) memory area instead of the input (I) memory area. The peripheral input memory area can be 
read as a byte, a word, or a double word. Therefore, a single digital input cannot be read via a 
contact (bit) element. 
To conditionally pass voltage depending on the status of an immediate input: 
1.  A word of PI memory that contains the input data of concern is read by the CPU. 
2.  The word of PI memory is then ANDed with a constant that yields a non-zero result if the input 
bit is on ("1"). 
3.  The accumulator is tested for non-zero condition. 
Example 
Ladder Network with Immediate Read of Peripheral Input I1.1 
 
WAND_W
EN
OUT
IN2
ENO
IN1
16#0002
PIW1
MWx *
I 4.1
<>0
I 4.5
 
 

MWx has to be specified in order to be able to store the network. x may be any permitted 
number. 
 
Description of WAND_W instruction: 
PIW1             
0000000000101010 
W#16#0002   
0000000000000010 
Result          
0000000000000010     
In this example immediate input I1.1 is in series with I4.1 and I4.5. 
The word PIW1 contains the immediate status of I1.1. PIW1 is ANDed with W#16#0002. The result 
is not equal to zero if I1.1 (second bit) in PB1 is true ("1"). The contact A<>0 passes voltage if the 
result of the WAND_W instruction is not equal to zero. 

Bit Logic Instructions
 
1.18 Immediate Write
 
 
Ladder Logic (LAD) for S7-300 and S7-400 Programming 
30 
Reference Manual, 04/2017, A5E41524738-AA 