Runtime Test Cases
PLC Program to Call a Subroutine for a Different Process
This is a PLC Program to Call a Subroutine for a Different Process.


Problem Description
Add temperature outputs of two temperature transmitters and display the total temperature. Update
display every 10 seconds when this system is active using Subroutine program.
Problem Solution

Using subroutine has an advantage that process is not affected by any other data in subroutine program
unless and until the subroutine is called.

This is very useful in displaying various data on the same display with a particular time delay.

For example, we can use the same display to show Pressure readings for the first 5 seconds and
Temperature reading for the next five seconds and so on.

When we use subroutine instruction, Subroutine address must be same in JSR instruction of main program
and RET instruction of subroutine program.
PLC Program
Here is PLC program to Call a Subroutine for a Different Process, along with program explanation and run
time test cases.
List of Inputs and Outputs
I:1/0
= Start
(Input)
I:1/1
= Stop
(Input)
O:2/0
= Master Coil
(Output)
T4:0
= Time delay to update data
(Timer)
O:6
= Display address
(Output)
N7:0 & N7:1 = Temperature data of transmitters 
(Register)
T4:0/DN = Update display calling Subroutine, reset timer
(Timer Bit)
U:3
= Address of Subroutine
(Subroutine)


Ladder
 
Diagram
 
to
 
call
 
subroutine
Program Description

Main program comprises of simple Master Coil rung, rung for timer and rung to call subroutine.

When Start PB I:1/0 is pressed, Master coil energizes and the TON timer T4:0 is enabled.

After 10 seconds when PRESET=ACCUMULATOR, T4:0/DN bit goes high calling subroutine.

Subroutine has a program that adds two data from addresses N7:0 and N7:1 which are outputs from
Temperature transmitters. These outputs are added and output of addition is converted into BCD and sent to
address O:6 which is connected to Display.

Output data are in Hexadecimal and Displays accept BCD inputs. So TOD instruction is used here to
convert data of temperature addition to BCD.

T4:0/DN is also used as an XIO input to Timer itself, hence it automatically resets to 0 whenever preset and
accumulator values are equal or in other words, it updates the display every 10secs resetting timer.