Problem Description
One open tank is installed in the plant of which liquid level is to be controlled. When level reaches the
Level Low, Outlet flow is blocked and inlet flow is allowed until high level is achieved. And when Level
High is detected, outlet flow is allowed and inlet flow is blocked.
Problem Diagram
Diagram of a single tank level control
Problem Solution

To detect high and low level of liquid in the tank, two level switches are used which gives output in digital
terms, that is when corresponding levels are detected, it gives output high otherwise remain low.

To control level of this system, Single Acting piston valve can be used which has two states, either fully open
or fully close.

Low Level Switch is mounted at the bottom of the tank and Level High switch mounted at the side upper
most position.

When this inputs are detected, output to Control Valve has to be latched in order to continuously fill or empty
the system.

Master start/stop is also provided to shut down or start the entire process.
PLC Program
Here is PLC program to Control Level of a Single Tank, along with program explanation and run time test
cases.
List of Inputs and Outputs


 I:1/0
= Level High Switch
(Input)
I:1/1
= Level Low Switch
(Input)
O:2/0
= Inlet Valve
(Output)
O:2/1
= Outlet Valve
(Output)
I:1/14 = Start
(Input)
I:1/15 = Stop
(Input)
Ladder
 
Diagram
 
to
 
control
 
this
 
process
Program Description

RUNG000 is simply for latching a coil and master start-stop buttons.

RUNG001 is to control the outlet valve through O:2/1. This is done when Level High is detected.

Latching of Output O:2/1 is done because when High Level is detected, input to RUNG001 is temporary, like
Push Button. So in order to keep outlet valve open until the Level Low I:1/1 is detected, latching is done. XIO of
Level Low Switch is connected in series so that when Level Low is detected, it goes true closing the outlet valve.

Similarly in RUNG002, it works exactly same. The only difference in RUNG002 is that extra I:1/14 contact in
parallel with LLS.

Suppose when the system is started and the tank is partially filled, neither LHS nor LLS is detected, in this
case, outlet and inlet valves remain closed while inlet valve should open to start filling the tank because it’s