Electrical design and installation of solar pumps


terminal block (or motor MCB) provided for this purpose



Yüklə 1,99 Mb.
Pdf görüntüsü
səhifə22/37
tarix25.09.2023
ölçüsü1,99 Mb.
#148570
1   ...   18   19   20   21   22   23   24   25   ...   37
acf solar pumping electrical design and installation of solar pumps guidelines 2020

terminal block (or motor MCB) provided for this purpose.
You can never connect a generator directly to the pump, even via a changeover, because by doing so, all safety features become 
nonfunctional, particularly the low level water sensor in the borehole.
If there is no need for a generator permanently connected to the pumping system, then we will avoid installing 
one altogether. Installing a permanent generator when not necessary can be seen as a bonus or an extra for the 
beneficiaries, but it is not.
The installation of a permanent generator requires fuel storage, oil, spare parts, regular start-ups for maintenance, drained oil 
treatment or dumping ... and therefore a significant additional cost for the beneficiary community.
The sizing rules of backup or complementary generator sets are identical (see calculation chapter). The generator output 
voltage must be compatible with the power supply of the pump controller or pump inverter. 
Standard specifications for generator installation should also be applied to generators installed for pumping sites (slab 
thickness, clearance around the machine, cooling air flow, fire extinguisher ...).


23
SOLAR PUMPING
Guidelines - Electrical design and installation of solar pumps
11
WATER LEVEL DETECTION IN THE TANK
Water level detection can be useful to:

Automatically start and stop the water pump when water level is low in the tank and when tank is full (avoid overflowing 
and water loss).

Run alarms (lights, sound alarms, indicators …).

Know the level of water in the tank when the tank is hardly accessible due to its height, or when the tank is located far away 
from the borehole or distribution point. 
To perform these functions, two main categories of sensors can be used:

« Free-volt contact » sensors. These sensors will work as a switch, will open or close when a certain level is reached. 
It is not possible to accurately measure the level with this type of probe and display it in m3. They are only used to 
send punctual signals, typically «pump start», «empty tank», «pump stop», ...

Potentiometric probes, commonly called « 4/20 milliamps » for the current value they allow: 4 mA of current for 
minimum value (tank empty) and 20 mA for maximum value (tank full). These sensors can measure the level of water 
with 1cm of precision, send this information to an electronic calculator, that will convert the signal in m3 and display 
it on a screen. In addition, these calculators can also switch on or off some pre-programmed « free-volt contact », as 
explained above. 