CALCULATION OF DIESEL GENERATOR POWER
When powered by a variable energy source, such as solar panels that produce more or less depending on sun power, pump
start-ups are progressive. This is not the case when pumps are powered by a generator.
After the generator starts, when the output circuit breaker of the genset is switched on, the pump is powered suddenly and
reaches its full power in some milliseconds. This sudden increase of power of the electric motor generates strong magnetic
fields, which the generator must overcome before the electric motor can start. This phenomenon is called a «load impact at
start-up».
If you choose a generator with the same power as the pump (eg 2.2 kVA for a 2kW pump), it will be unable to start the pump.
Concretely the engine of the generator set will stall brutally.
To avoid it, we apply the following calculation formula: