Problem Solution
To detect level of Material A and Material B, two separate level switches are used.
And to detect low level, one more level switch is used at the bottom of the tank.
These give output in digital terms that is when corresponding levels are detected.
To control level of this system, Single Acting Piston valve can be used which has two states, either fully
open or fully close.
To control mixing, agitator is used which is connected with Motor shaft.
Heater is installed inside the tank and temperature sensor such as RTD or Thermocouple is used to detect
the temperature of liquid in the tank.
This mixer is mixed until set point temperature is achieved.
Outlet valve is then operated to drain the mixed product.
PLC Program
Here is PLC program for Heating and Mixing of Products, along with program explanation and run time
test cases.
List
of Inputs and Outputs
I:1/14 =
Start
(Input)
I:1/15 = Stop
(Input)
B3:0/0 =
Master Coil Bit
(Bit)
I:1/0
=
Level of Material B
(Input)
I:1/1
=
Level of Material A
(Input)
I:1/2
= Low Level Switch (empty tank)
(Input)
O:2/0
= Inlet Valve 1 (Material A Feed) (Output)
O:2/1
= Inlet Valve 2 (Material B Feed) (Output)
O:2/2
= Agitator Motor (Mixing)
(Output)
O:2/3
= Heater
(Output)
O:2/4
= Outlet
valve to drain the product
(Output)