PLC-4

Ladder
 
Diagram
 
to
 
heat
 
and
 
mix
 
materials
Program Description

RUNG000 contain master start/stop with address of Start PB I:1/14 and Stop PB I:1/15.

RUNG001 is to operate Inlet Valve of Material A with address O:2/0. It is operated when Low Level of the
tank is detected by Level Low Switch I:1/2. And it is closed when Inlet Valve of material B starts that is when
Level Material A is detected by a switch with address I:1/1. Start PB is also connected in parallel with the LLS, it
is done so that when LLS or level of Material A is not detected, Inlet Valve is operated by Start PB.



RUNG002 is to operate Inlet Valve of Material B with address O:2/1. It is opened when Material A is filled to
its desired level (Level Material A). In other words, Valve of Material B is opened when Level of Material A is
detected by I:1/1 and it is closed when Level of Material B is detected or Tank is full.

RUNG003 operates Agitator Motor and Heater with address O:2/2 and O:2/3 respectively. When the tank is
full with Material A and B, Level High (Level Material B) is detected. Agitator Motor is connected to the address
O:2/2 and Heater to O:2/3. Agitator and Heater are run when I:1/0 is set to 1 that is when tank is full.

RUNG004 is for Outlet Valve with address O:2/3. It is operated when the entire mixing and heating process
is completed that is when temperature set point is reached. And this valve closed again is closed when LLS is
again detected.
Runtime Test Cases
Inputs
Outputs Physical Elements
I:1/2 = 1
O:2/0 = 1 Open Inlet Valve 1
I:1/2 = 0 and I:1/1 = 0
O:2/0 = 1 Open Inlet Valve 1
I:1/1 = 1
O:2/0 = 0
Close Inlet Valve 1
I:1/1 = 1
O:2/1 = 1 Open Inlet valve 2
I:1/0 = 1
O:2/1 = 0 Close Inlet Valve 2
I:1/0 = 1
O:2/2 = 1, O:2/3 = 1
Run Agitator Motor and Heater
Temperature ≥ 70°C
O:2/2 = 0, O:2/3 = 0
Stop Agitator Motor and Heater
Temperature ≥ 70°C
O:2/4 = 1 Open Outlet Valve
I:1/2 = 1
O:2/4 = 0 Close Outlet Valve
PLC Program to Heat the Liquid in Tank by Steam Flow