List
of Inputs and Outputs
I:1/0
= Master Switch
(Input)
I:1/1
=
Deactivate system
(Input)
I:1/2
= Motion Detector
(Input)
I:1/3
=
Window Sensor
(Input)
I:1/4
= Button to Stop Alarm (not the system)
(Input)
O:2/0
= Master Coil
(Output)
O:2/1
=
Alarm Coil
(Output)
O:2/2
= Alarm
(Output)
Ladder
Diagram
for
Burglar
Alarm
Security
System
Problem Description
RUNG000 simply shows a latching of a coil O:2/0 to activate the entire security system.
When Activate button I:1/0 is pressed momentarily, the security system is activated.
If the system is not activated, alarm does not indicate anything since sensors will have no effects on the
Alarm Coil O:2/1.
When system is active and Motion detector detects a person, the alarm coil
will momentarily go high
activating the Alarm O:2/2 which stays ON until I:1/4 is pressed manually.
As we can see in RUNG001 that XIO (Normally Closed) contact is used for Window Sensor input I:1/3
because it is normally in true state when not activated. So when the breakage of a window is detected, it goes
false from its true condition allowing Alarm Coil O:2/1 to go high for a moment which in turn activates Alarm
O:2/2.
In RUNG002, latching has to be provided in order to keep the alarm ringing even if the detection by the
sensors are momentary or to be accurate, pulsating.